SAKSHAM-345 is an ideal fit for Advanced Metering Infrastructure (AMI) systems intended for load management, multi-rate / Time-of-Use, and anti-theft metering of residential and light commercial consumers with Three-phase service connections. It measures, collects, analyzes, controls energy usage, and communicates with Head End System either on request or on a schedule. This gives unparalleled end-to-end visibility to the utilities into their distribution networks.
Connection Type | Three Phase 4 wire direct connected | LED Indicators | LED Pulse imp/kWh,
LED Network status |
Standards | IEC 62052-11, IEC 62053-21 IS 13779, IS 18444, IS 15959, CBIP-325 | Communication Ports | Optical Port IEC 62056-21 Modular GSM/GPRS/2G/3G/4G/NBIOT Dual Band 900/1800 MHz SIM card exchangeable/replaceable in field Extemal Antenna (option) |
Metrology Accuracy | Class-1 | Communication Protocol | DLMS COSEM |
Rated Voltage | 230V/240V(-40% to +20%) | Operating Temperature Range | -10°C to +55°C |
Rate Current | lb (Imax) A=10(60)A, 20(100)A
Withstands 120% Imax. |
Storage Temperature Range | -25°C to 70°C |
Starting Current | 0.4% ib | Relative Humidity | Up to 95% Non condensing. |
Frequency | 50Hz±5% | Degree of Protection | IP51 |
Burden-Voltage Circuit | <5W/15VA | ||
Burden-Voltage Circuit | <4VA | ||
Load Contactor | Latching relay in Three Phase Max Current 120A | ||
Display | STN LCD with Backlight |